Skip to main content

Pressure Enthalpy chart



Pressure Enthalpy Chart

It is a chart used to explain and analyze refrigeration and air conditioning systems. It consist of pressure on ordinate axis and enthalpy on abscissa. 

Before explaining the pressure enthalpy chart(shown in fig) lets discuss about some common terms that will be used.

Pressure lines: Pressure lines originated from vertical axis (y-axis) and are horizontal lines drawn parallel to abscissa (x-axis). (light blue line in fig)

Enthalpy lines: Enthalpy lines originated from horizontal axis and are vertical lines drawn parallel to vertical axis(Y-axis). (Red color in fig)

Critical point: Critical point separate the saturated liquid and saturated vapor curve.

Critical temperature: Critical temperature is the temperature above which the vapor can never be liquefied at any pressure. to liquefied vapor, temperature must be reduced.

Critical Pressure:  It is the pressure above which the vapor can never be liquefied at any temperature. To liquefied the vapor, Pressure must be reduced.

Saturated liquid curve: It is the left side curve of bubble, where refrigerant is in saturated liquid state at corresponding pressure.

Saturated Vapor curve: It is the right side of the bubble, where refrigerant can be found in complete vapor form at corresponding pressure. 

Sub-cool region(l): The left side of bubble till critical pressure is where refrigerant present at lower temperature than the  saturated temperature is sub-cool region of Pressure enthalpy chart.

Super-heat region (v): The right side of bubble, where refrigerant found in super-heat condition (temperature of refrigerant is more than the saturated vapor temperature) is super-heat region of pressure-Enthalpy chart.

Liquid-vapor mixture region: the space in between the bubble where refrigerant found in both vapor and liquid state.

Temperature lines: These lines are almost vertical lines in subcool and superheat region and horizontal in between bubble (liquid vapor mixture). (green lines in fig)

Specific volume lines: These lines originated from saturated vapor curve and are at an angle to horizontal. (dark blue in fig)

Entropy lines: These lines originated from saturated vapor lines and move upward with an angle from vertical lines. (orange lines in fig)


Fig.

In an ideal refrigeration cycle following processes follow.


Compression: The refrigerant enters the compressor in saturated state where it is compressed isentropically from evaporator pressure (low pressure) to condenser pressure using external work. Every refrigerant have a temperature with a pressure and refrigerant have a specified pressure at ambient temperature. So main work of compressor is to compress the refrigerant above that pressure.  In compressor, the pressure and temperature of refrigerant increase. The entropy of refrigerant at suction and discharge remains same.


W_compressor= m_ref*(h2-h1)            (1)

where: m_ref= mass flow rate of refrigerant
           h1=enthalpy at evaporator outlet
           h2=enthalpy at compressor outlet.

Condensation: The refrigerant enters in condenser in superheated condition. So first the refrigerant desuperheated till condenser temperature. This is done in initial length of condenser and in discharge pipe. Then refrigerant is condensed at constant temperature and pressure (in case of zeotropic blends, pressure and temperature change during phase change). the refrigerant is in saturated liquid state at the end of condenser.

HRR=m_ref(h2-h3)                               (2)

where: HRR= heat rejection rate
            h2= enthalpy at discharge
            h3=enthalpy at condenser outlet


Expansion: The saturated liquid from condenser enters into expansion tube either a capillary tube or expansion valve. The high pressure  liquid refrigerant flow through the expansion device and experience reduction in pressure which ultimately reduce the temperature. At the inlet of capillary, refrigerant is in pure liquid form but at outlet it has some vapor along with it while entering in to evaporator. The amount of vapor at capillary outlet depend upon the difference in pressure of evaporator and condenser. More the difference, more will be vapor. because the refrigerant has to evaporate more to reduce overall temperature by converting latent heat in to sensible heat. (as latent heat is approximate 1000 times the sensible heat). 
First law of thermodynamics holds good for expansion device as below:

m_ref*cp_l*(T3-T4)=m_ref*h_fg*x      (3)

 x=(h4-h1)/(h_fg)                                      (4)

where: m_ref=mass flow rate of refrigerant
            cp_l=specic heat for liquid refrigerant
            h4=enthalpy at evaporator inlet
            h1=enthalpy at compressor inlet
            h_fg=latent heat of vaporization of refrigerant at evaporator temperature.
            x=amount of vapor present at evaporator inlet (dryness fraction)

The left hand side of equation 3, is the sensible cooling which refrigerant undergo while right hand side the latent heat.
         
As principle of expansion devices is evaporative cooling. please refer below link for more:

 http://athermocreation.blogspot.in/2017/10/evaporative-cooling.html.

Vaporisation(cooling):  Vaporization of refrigerant occur in evaporator, where it take the heat from surrounding and produce the refrigeration effect by vaporizing itself in evaporator.

m_ref*(h1-h4)=m*(1-x)*h_fg=NRE        (5)

where: NRE=Net refrigerating effect
            m_ref=mass flow rate of refrigerant
            h1=enthalpy of refrigerant at evaporator outlet
            h4=enthalpy of refrigerant at evaporator inlet
            x=dryness fraction of refrigerant at evaporator inlet.

Coefficient of performance:  It is the ratio of net cooling effect to the compressor work done.

COP= (h1-h4)/(h2-h1)                                (6)


Heat Rejection factor: It is the ratio between the heat rejected in condenser to heat absorbed in evaporator.

HRF=(h2-h3)/(h1-h4)                                  (7)

where HRF= heat rejection factor
           h4=enthalpy at evaporator inlet


Difference between ideal PH chart and Real PH chart:  (!) In reality, refrigerant enter in the compressor in superheated state rather than in saturated vapor state. So that liquid refrigerant do not enter in to the compressor under any condition. It is done either by expansion valve or in case of capillary by capillary suction heat exchanger.
(2) Second difference is that after exiting from the condenser, refrigerant is cooled below its saturated temperature to increase the refrigeration effect by reducing the amount of vapor present at evaporator inlet.
(3) Third difference is that, the compression of refrigerant is n completely not an isentropic process practically. Because as per second law process occur only if there is an increase in universal entropy.
(4) The work done of compressor is more than the ideal work done because there is loss of heat in windings of compressor and also from compressor top by circulating oil to take heat from compressor and exit it to surrounding.
(5) Also the pressure of refrigerant at suction is not same as that of evaporator due to pressure loss in evaporator and suction tube.
(6) In condenser there is also loss of pressure due to fluid flow. Pressure loss should be minimized by proper selection of equipment and pipes of proper diameters and proper movement of refrigerant.


Comments

Popular posts from this blog

Numerical designing (Mathematical modelling) of an air conditioner ( by two methods)

Human do not feel comfort at  high temperatures or extremely low temperatures. The situation of body when it feel comfort with the surrounding conditions like temperature, RH%, air flow etc is called the thermal comfort. This comfort situation is at 27 DBT and 19 WBT.  To provide this thermal comfort condition, Air conditioners are used which supply the air at required temperatures. The schematic of an air conditioner is shown as below: Consider a 1 TR air conditioner with ambient 35 DBT and 24 WBT and indoor design conditions are 27 DBT and 19 WBT . So the inlet air to evaporator is at 27 DBT and 19 WBT. The design conditions are as per below: Outdoor conditions: 35 DBT, 24 WBT Indoor conditions: 27 DBT and 19 WBT Evaporator temperature in: 12 deg C Evaporator temperature out: 15 deg C Condensing temperature: 54 deg C Liquid temperature: 46 deg C (ASHRAE conditions) Now main thing to calculate is required mass flow rate of air (CFM) and air out condition from

Evaporative cooling

Evaporative cooling is the basic of mostly all refrigeration technology that involve a phase change in refrigerant. The Evaporative technology is used in Hot and dry areas. In these areas it is more effective and cost efficient than the air conditioners. But in humid areas, Evaporative cooling does not bring thermal comfort. Thermal comfort is a state where our body feel good with respect to temperature of surrounding. Working principle Evaporative cooling: For Moist air:     When hot and dry air pass through an evaporative pad (a wet pad, with same water quantity always during evaporative process), It take some water(wet vapor form) from pad and the heat require to evaporate water is taken from water itself. As latent heat is almost 100 times the sensible heat for water, So a small portion of water will evaporate, resulting in overall reduction of temperature of water and air leaving the air and water at wet bulb temperature of entering air. (refer to figure) For Exam

Numerical design (Mathematical modelling) of a compressor for refrigeration and air conditioning(cylinder volume calculation)

Compressor is the heart of any refrigerating equipment as it pump the refrigerant in to the all components like our heart supply the blood throughout the body parts. Compressor decide the cooling capacity and power consumption for refrigerating machine. Its main work is to take the refrigerant from suction pipe at very low pressure(temperature as well) and compress it to a very high pressure (discharge pressure). As we all know that refrigerant condense in condenser at constant temperature (for zeotropic blends it vary), and that temperature is corresponding to the discharge pressure of refrigerant. Discharge pressure of refrigerant is such that its corresponding temperature should be higher than the ambient temperature only than refrigerant will condense in to liquid if the discharge saturation temperature(corresponding to discharge pressure) is lower than the ambient temperature, than refrigerant will not condense. All compressors can be described on their application(use) as